Commands Below are in Hex Format using API Mode. TX = Bytes Sent to the Controller RX = Bytes Received from the Controller. Note Bytes Received May be Different for Some Commands.
R = RelayB = Bank
CK = Checksum
TX: | 2 | 3 | R | B | CK | Function: | RX: | 2 | 3 | CK |
---|---|---|---|---|---|---|---|---|---|---|
AA | 03 | FE | 64 | 01 | 10 | Turn Off Relay 1 in Bank 1 | AA | 01 | 55 | 00 |
AA | 03 | FE | 65 | 01 | 11 | Turn Off Relay 2 in Bank 1 | AA | 01 | 55 | 00 |
AA | 03 | FE | 66 | 01 | 12 | Turn Off Relay 3 in Bank 1 | AA | 01 | 55 | 00 |
AA | 03 | FE | 67 | 01 | 13 | Turn Off Relay 4 in Bank 1 | AA | 01 | 55 | 00 |
AA | 03 | FE | 68 | 01 | 14 | Turn Off Relay 5 in Bank 1 | AA | 01 | 55 | 00 |
AA | 03 | FE | 69 | 01 | 15 | Turn Off Relay 6 in Bank 1 | AA | 01 | 55 | 00 |
AA | 03 | FE | 6A | 01 | 16 | Turn Off Relay 7 in Bank 1 | AA | 01 | 55 | 00 |
AA | 03 | FE | 6B | 01 | 17 | Turn Off Relay 8 in Bank 1 | AA | 01 | 55 | 00 |
AA | 03 | FE | 64 | 02 | 11 | Turn Off Relay 1 in Bank 2 | AA | 01 | 55 | 00 |
AA | 03 | FE | 64 | 03 | 12 | Turn Off Relay 1 in Bank 3 | AA | 01 | 55 | 00 |
AA | 03 | FE | 64 | 04 | 13 | Turn Off Relay 1 in Bank 4 | AA | 01 | 55 | 00 |