The following relay timer commands will configure the timer values only, but will NOT activate the timers.  Timer activation is handled by the “Relay Timers: Pause and Resume” section of this guide.

T = Timer
HR = Hours
MN = Minutes
SC = Seconds
R = Relay
CK = Checksum
TX:234THRMNSCRCKFunctionRX234
AA07FE325A0000050040Relay 0 On for Duration of 5 Seconds using Timer 0AA015500
AA07FE326E0000050054Pulse Relay 0 using Timer 0 after 5 SecondsAA015500
AA07FE323300000A001ERelay 0 On for Duration of 10 Seconds using Timer 1AA015500
AA07FE326E00000A0059Pulse Relay 0 using Timer 1 after 10 SecondsAA015500
AA07FE32690100001F6ARelay 31 On for Duration of 1 Hour using Timer 15AA015500
AA07FE327D0100001776Pulse Relay 23 using Timer 15 after 1 HourAA015500
AA07FE3265000A001565Relay 21 On for Duration of 10 Min. using Timer 11AA015500
AA07FE327C0014001687Pulse Relay 22 using Timer 14 after 20 MinutesAA015500