The following relay timer commands will configure the timer values only, but will NOT activate the timers. Timer activation is handled by the “Relay Timers: Pause and Resume” section of this guide.
T = TimerHR = Hours
MN = Minutes
SC = Seconds
R = Relay
CK = Checksum
TX: | 2 | 3 | 4 | T | HR | MN | SC | R | CK | Function | RX | 2 | 3 | 4 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AA | 07 | FE | 32 | 5A | 00 | 00 | 05 | 00 | 40 | Relay 0 On for Duration of 5 Seconds using Timer 0 | AA | 01 | 55 | 00 |
AA | 07 | FE | 32 | 6E | 00 | 00 | 05 | 00 | 54 | Pulse Relay 0 using Timer 0 after 5 Seconds | AA | 01 | 55 | 00 |
AA | 07 | FE | 32 | 33 | 00 | 00 | 0A | 00 | 1E | Relay 0 On for Duration of 10 Seconds using Timer 1 | AA | 01 | 55 | 00 |
AA | 07 | FE | 32 | 6E | 00 | 00 | 0A | 00 | 59 | Pulse Relay 0 using Timer 1 after 10 Seconds | AA | 01 | 55 | 00 |
AA | 07 | FE | 32 | 69 | 01 | 00 | 00 | 1F | 6A | Relay 31 On for Duration of 1 Hour using Timer 15 | AA | 01 | 55 | 00 |
AA | 07 | FE | 32 | 7D | 01 | 00 | 00 | 17 | 76 | Pulse Relay 23 using Timer 15 after 1 Hour | AA | 01 | 55 | 00 |
AA | 07 | FE | 32 | 65 | 00 | 0A | 00 | 15 | 65 | Relay 21 On for Duration of 10 Min. using Timer 11 | AA | 01 | 55 | 00 |